NF-CP Moulded Case Circuit Breaker
|
|
|
Application
|
|
NF-CP moulded case circuit breaker is available in three ranges, standard, hi- break. The performance of the NF-CP range is the result of extensive design & development-utilizing AAD accredited test station. The current limiting action of
NF-CP provides low values of let-through energy. Full information for this and time/current characteristic curves are both available on request to provide more information.
|
|
Main Technical Specifications
|
|
Type
|
Rated current of
trip (In A)
|
Pole
number
|
(P1/P2) Ica/Ics breaking capacity(kA)
|
230 |
400 |
440 |
500
|
NF-50CP
|
5,10,15,20,30,40,50
|
3P
|
5/2
|
5/2
|
2.5/1
|
2.5/1
|
NF-60CP
|
60
|
3P
|
5/2
|
5/2
|
2.5/1
|
2.5/1
|
NF-100CP
|
60,75,100
|
3P
|
25/10
|
10/5
|
10/5
|
7/4
|
NF-250CP
|
125,150,175,200,225,250
|
3P
|
30/10
|
18/9
|
15/8
|
10/5
|
NF-400CP
|
250,300,350,400
|
3P
|
50/25
|
35/18
|
25/13
|
15/8
|
|
|
|