HCL1-63 Residual Current Device
|
|
|
Technical data
|
|
Standard
|
IEC1008,GB16916,BS EN61008
|
Rated Voltage (Un)
|
2pole:230V AC
|
Rated Current (In)
|
25,40,63A
|
Rated residual operating current (l△n)
|
30,100,300,500mA
|
Rated residual non-operating current (l△no)
|
0.5 l△n
|
Residual current off-tine
|
≤0.1s
|
Minimum value of rated making and breaking capacity (lm)
|
1KA
|
Rated conditional short-circuit current (lnc)
|
ln=25,40A Inc=1500A
|
ln=63A Inc=3000A
|
Endurance
|
on load:2000cycles
|
off load:2000cycles
|
|
|
INSTALLATION
|
|
On symmetrical DIN rail
|
|
|
|
|